First Out Annunciator

The First Out Indicator is designed to be a cost effective means of adding diagnostics to a machine to detect faults in the operational and safety circuits of electrical equipment.  The First Out Indicator monitors up to eight points in a series string of contacts, such as proxs, limit switches, photo eyes, contactors, push-buttons, relay contacts, etc.  The First Out Indicator will latch and hold the first failed contact in a string and indicate that fault.  If more that eight points need to be monitored, two or more units can be combined.

Performance Specifications

Power Requirements: 120 VAC +/- 10%, 50/60 Hz
Temperature Range: 0-40 degrees C
Input: Up to 8 inputs to a single board.  Expandable in multiples of 8
Fault Detection: Detects voltage across an open contact. (Specify voltage during model selection)
Time Delay Between Fault and Indication: 8m Sec. maximum
Output: 24 VDC @ 30 mA each (8 outputs)
Output Relay: Form C contact.  One amp, 125 VAC; 2 amps, 28 VDC
Reset: By reset push-button or by removing power
Lamp Test: Turns on all lights.  Does not affect indication if fault is present or if fault occurs during lamp test

Model Selection
Part Number Description Voltage Sense Range
P5038-0101 First Out PC Based 8 Port 6-36 VAC/DC
P5038-0102 First Out PC Based 8 Port 37-149 VAC/DC
P5038-0103 First Out  PC Based 8 Port 150-300 VAC/DC
 

  